DISTRIBUTION

 

x

OPW00201

  • Open Frame 1phase Fixed Output TS35mm DIN EN 50022
Data sheet (PDF)

 




OPW00201

Model OPW00201
Power 20W
Nominal AC Input 100... 240Vac
Input Range AC 90... 265Vac
Input Range DC 120... 375Vdc
Input Frequency 47... 63Hz
Hold-Up Time 50ms
Inrush Current Protection 495mAeff / 700mApeak active limiter ±5%
Autostart Soft start
Output Voltage 5V 12V 24V 48V
Adjust Range Uout 4,9... 5,5V 11,4... 23,2V 23,5... 28,5V 45,6... 52,8V
Ripple & Noise mVss 50mV 25mV 80mV 40mV
Nominal Output Current 4A 1,7A 850mA 420mA
Power Boost <=60°C/60s 20%
Stability at Load Switch ±0,5%
Transient Time tba
Efficiency 84%
Basic load Idling-proof
Short Circuit Protection Continuous
Ambient Operation Temperature -20°C... +75°C
Cooling Natural convection
Temperature Monitoring Yes
Dimensions (WxHxD) 120x70x27mm
IP-Range Open Frame
Safety Norms CE
Safety IEC EN60950-1 EN50178
Safety Class 1(A) VDE0100 VDE0805
Input to Output Isolation 3000Vac
Climatic Class, Humidity 3k3, 90% non condensing
EMI EN55022B EN61000-3-2A
EMS EN61000-6-2,3 D
MTBF IEC61709 500000h
Power Good Relay No, for +5V TTL-Signal Series
Sense operation No
Remote Shutdown No
Features Active PFC, low inrush current
Ordering options None
Options See datasheet