DISTRIBUTION

 

x

HSR02401LIRC Redundant

  • DIN-Rail redundant 1phase Fixed Output TS35mm DIN EN 50022
  • Low Inrush

 

Data sheet (PDF)

 




HSR02401LIRC redundant

Model HSR02401LIRC redundant
Power 240W
Nominal AC Input 115/230Vac
Input Range AC 90..115Vac/184..265Vac
Input Range DC 250... 375Vdc
Input Frequency 47... 63Hz
Hold-Up Time 50ms
Inrush Current Protection 10,6Aeff / 15Apeak active protection ±5%
Autostart Soft start
Output Voltage 12V 15V 24V 48V 60V
Adjust Range Uout 22,5... 28,5V 45,6... 52,8V 22,5... 28,8V 45,6... 52,8V 57,0... 66V
Ripple & Noise mVss 30mV 30mV 20mV 50mV 50mV
Nominal Output Current 15A 14A 10A 5A 4A
Power Boost <=60°C/60s 18A 16,8A 12A 6A 4,8A
Stability at Load Switch ±0,5%
Transient Time  
Efficiency 91%
Basic load Idling-proof
Short Circuit Protection Continuous
Ambient Operation Temperature -20°C... +70°C
Cooling Natural convection
Temperature Monitoring Yes
Dimensions (WxHxD) 120x124x96mm
IP-Range IP20
Safety Norms CSA UL CE according to IEC60950-1
Safety IEC EN60950-1 EN50178
Safety Class 1(A) VDE0100 VDE0805
Input to Output Isolation 3000Vac
Climatic Class, Humidity 3k3, 90% non condensing
EMI EN55022B
EMS EN61000-6-2,3
MTBF IEC61709 500000h
Power Good Relay Yes
Sense operation No
Remote Shutdown No
Features Built-in redundant decoupling diodes, low inrush current
Ordering options Protective coating
Options See datasheet