DISTRIBUTION

 

x

HSD10001

  • DIN-Rail Power Supply 3phase fix output TS35mm DIN EN 50022
  • Active Inrush Current Protection
  • Active PFC
  • Temperature Control
  • Clean C/V chart without foldback, ideal for dc drives and dc-UPS
  • Remote Shutdown
Product Information (PDF) STEP-Datei (STP) Data Sheet (PDF)

 




HSD10001

Model HSD10001
Power 960W/1080W
Nominal AC Input 3PH 400... 500Vac
Input Range AC 3PH 340... 575Vac
Input Range DC 450... 820Vdc
Input Frequency 47... 63Hz
Hold-Up Time 12ms
Inrush Current Protection 14,2Aeff / 20Apeak active protection ±6%
Autostart Soft start 50ms
Output Voltage 12V 24V 36V 48V 60V 72V
Adjust Range Vout 10,,, 17V 22... 30V 32... 43V 43... 53V 53... 72V 68... 86V
Ripple & Noise mVpp 50mV 50mV 80mV 100mV 100mV 150mV
Nominal Output Current 60°/40°C 50/55A 40/44A 28/31A 21/23A 17/18A 14/15A
Power Boost <=60°C/60s 55A 44A 30,8A 23,1A 18,7A 15,4A
Stability at Load Switch ±0,5% ±0,2% ±0,2% ±0,2% ±0,2% ±0,2%
Transient Time < 1ms
Efficiency 92,50%
Basic load Idling-proof
Short Circuit Protection Continuous
Ambient Operation Temperature -20°C... +70°C
Cooling Natural convection
Temperature Monitoring Yes
Dimensions (WxHxD) 200x131,5x124mm
IP-Range IP20
Safety Norms CSA UL CE according to IEC60950-1
Safety IEC EN60950-1 EN50178 EN60204-1
Safety Class 1(A) VDE0100 VDE0805
Input to Output Isolation 3000Vac
Climatic Class, Humidity 3k3, 95% non condensing
EMI EN55022B
EMS EN61000-6-2,3
MTBF IEC61709 500000h
Power Good Relay Yes
Remote Shutdown Yes
Features Active PFC, 2phase operation
Ordering options Protective coating
Options See datasheet