CPS-EP2000 2000W 19-Inch Rack-Mount & Wall-Mount
- V programming with internal poti
- OCP & OVP
- Current Share Bus for N+1 parallel operation
- Sense Mode
- Current Monitoring
- Remote Shutdown
- Inhibit (Interlock)
- DC & AC Power Good Relay open/center/close
- Fan Monitoring
- Temperature OT alarm
- 6kW in a 2U & 10kW in a 3U subframe
- Hard mount in 90° steps
CPS-EP2000
Model | CPS-EP2000 | ||||
Continuous Power | 2000W | ||||
Nominal Input Voltage | 230Vac | ||||
Input Voltage Range AC | 184-264Vac | ||||
Input Voltage Range DC | 250-375Vdc | ||||
Hold-up Time | 30ms | ||||
Inrush Current AC | Electronic Inrush Current Limiter 14,6Arms | ||||
Startautomatic | Softstart 100ms | ||||
Vout | 24V | 36V | 48V | 72V | 110V |
Vout prog. with poti | 24-30V | 30-45V | 45-58V | 58-90V | 90-150V |
Aout | 84,0A | 56,0A | 42,0A | 28,0A | 18,2A |
Ripply & Boise mVpp | 35mV | 35mV | 75mV | 100mV | 200mV |
Efficiency | 94% | ||||
Basic Load | Idling-proof | ||||
Short Cicuit Protection | Continuous | ||||
Cooling | Stepless controlled fans from EBM-Papst flow front-to-rear | ||||
Dimensions | 84x126,4x444mm, 2U or 3U Embedded or hard mount in 90° steps | ||||
Safety Standards | EN61010-1, EN61010-2-201, EN62368-1, EN60204-1, EN60950-1 | ||||
Input- /Output Isolation | 3000Vac | ||||
EMI | EN55032 class B and class A depending on models | ||||
EMS | EN61000-6-2,3,4 | ||||
MTBF | 500.000h | ||||
Current Monitoring | 0-5Vdc | ||||
Inhibit (Interlock) | Yes | ||||
DC Power Good Relay | Yes | ||||
AC Power Good Relay | Yes | ||||
Sense Compensation | Yes | ||||
Remote Shutdown | Yes | ||||
Continous Mode | Yes | ||||
Current Share Bus | Yes | ||||
Fan Failure Monitor | Yes | ||||
Temperature Monitor | Yes |